SE-601 DC Ground-Fault Monitor
SE-601 DC Ground-Fault Monitor
SE-601 DC Ground-Fault Monitor


Function:
  • Ground-fault protection for ungrounded direct-current (dc) systems

Features:
  • Ten ground-fault set points from 1 to 20 mA
  • Ten ground-fault trip-time settings from 0.05 to 2.5 seconds
  • Microprocessor based - recalibration not required
  • Remote reset and indication
  • Non-volatile trip memory
  • Selectable fail-safe (undervoltage) or non-fail-safe (shunt) operating mode
  • Self-test function
  • DIN-rail, surface, and panel mounting
  • Five year warranty

Manuals and Data Sheets:

Typical Applications:
  • Ground-fault protection for an ungrounded dc bus
  • Used in power generation plants, locomotives and other people movers, battery banks

Minimum System Components:
The SE-601 requires an SE-GRM-series ground-reference module matched to the system voltage (e.g. SE-GRM125 for a 125-Vdc bus).

IEEE Device Numbers:
76G


Accessories:
MPU-16A-Y92A-96N
Watertight Cover
Allows relays to be used in a wet environment. NEMA 4 rating. Shown mounted on the MPU-16A.
MPU-16A-Y92A-96N: Watertight Cover
MPU-16A-Y92A-96N
Watertight Cover
PMA-60
Panel-Mount Adapter
Used for panel mounting an SE-601 or SE-70X-series ground-fault monitor. IP 53 and NEMA 3 rating, tamper resistant.
PMA-60: Panel-Mount Adapter
PMA-60
Panel-Mount Adapter
Used with: SE-601, SE-701, SE-703, SE-704
PMA-55
Panel-Mount Adapter
Panel mount an SE-601 or SE-70X-series ground-fault monitor.
PMA-55: Panel-Mount Adapter
PMA-55
Panel-Mount Adapter
Used with: SE-601, SE-701, SE-703, SE-704
SE-GRM
Ground-Reference Module
Input device for SE-601.
SE-GRM: Ground-Reference Module
SE-GRM
Ground-Reference Module
Used with: SE-601
Available for: 24Vdc - SE-GRM024,
48 Vdc - SE-GRM048, 125 Vdc - SE-GRM125,
250 Vdc - SE-GRM250, 500 Vdc - SE-GRM500, 780 Vdc - SE-GRM780.
Contact factory for other voltages