SE-330 Neutral-Grounding-Resistor Monitor
Functions:
- Detects neutral-grounding-resistor failure - NGR failure will render current-sensing ground-fault protection inoperative
- Detects ground faults
- Controls pulsing-ground-fault system
- Data logging with PC software
Features:
- Continuously measures NGR resistance
- Wide set-point ranges - compatible with any neutral-connected NGR up to 35-kV system voltage (for 72-kV system voltage see SE-330HV)
- Calibrates to NGR resistance
- 4-20 mA output for earth-leakage metering
- DFT (harmonic) filter prevents false operation
- Trip delay to coordinate with downstream ground-fault relays
- Standard RS-232 interface
- Optional DeviceNet, PROFIBUS, and Ethernet communications
- Four output relays for control and indication
- Pulsing output contact for fault locating
- Conforms to CSA Standard M421-00 Use of Electricity in Mines
- Free SE-MON330 PC-interface software
- Conformally coated circuit boards
- Five year warranty
Manuals:
Typical Applications:
- Resistance-grounded transformers and generators in processing, manufacturing, chemical, mining, forestry, petroleum, and water treatment facilities
- Tripping and alarm-only resistance-grounded systems, including overhead line and pulsing-ground-fault applications
- Compatible with very high and very low resistor values
- NGR monitoring is recommended for all resistance-grounded systems
Minimum System Components:
- The SE-330 requires a current transformer and a sensing resistor (ER-600VC, ER-5KV, ER-15KV, ER-25KV, or ER-35KV).
- Outdoor Sensing Resistor Applications
IEEE Device Numbers:
3GC, 50G, 50N, 51G, 51N, 59N, 86