SE-325 Neutral-Grounding-Resistor Monitor
Functions:
- Detects neutral-grounding-resistor failure - NGR failure will render current-sensing ground-fault protection inoperative
- Detects ground faults
Features:
- Continuously monitors NGR continuity
- Conforms to CSA Standard M421-00 Use of Electricity in Mines
- Meets the requirements of the Pennsylvania Bureau of Mine Safety
- Provides main or backup ground-fault protection
- Trip delay to coordinate with downstream ground-fault relays
- Selectable fail-safe (undervoltage) or non-fail-safe (shunt) operating mode
- LED indication of Ground Fault, Resistor Fault, and Power
- Conformally coated circuit boards
- Five year warranty
Typical Applications:
- Transformers and generators with a maximum 25-A NGR in processing, manufacturing, chemical, mining, forestry, petroleum, and water-treatment facilities
- NGR monitoring is recommended for all resistance-grounded systems
- Can be used with a zigzag transformer and an NGR to provide monitored resistance grounding to upgrade an ungrounded supply
- Pulsing ground-fault location systems
Minimum System Components:
- The SE-325 requires a CT200 current transformer and a sensing resistor (ER-600VC, ER-5KV, ER-15KV, or ER-25KV).
- Outdoor Sensing Resistor Applications
IEEE Device Numbers:
50G, 50N, 51G, 51N, 59N, 86