PGR-8800 Arc-Flash Relay
PGR-8800 Arc-Flash Relay
PGR-8800 Arc-Flash Relay

PGR-8800 Light Sensors
PGA-LS10 and PGA-LS20 Light Sensors




Functions:
  • The PGR-8800 limits arc-flash damage by detecting the light from an arc-flash event and tripping rapidly
  • Current transformer (CT) input provides overcurrent protection and prevents nuisance trips

Features:
  • Detects an arc flash and trips the output in less than 1 ms
  • Six inputs for PGA-LS10 Point Sensors and PGA-LS20 Fiber-Optic Sensors
  • Link up to 4 PGR-8800 units together; all units trip when one senses an arc flash
  • Adjustable light sensitivity
  • Built-in sensor
  • Continuous monitoring of sensors and redundant trip circuit
  • Remote-trip, trip-inhibit, and reset inputs
  • Separate connection for 24-Vdc battery power with built-in battery charging circuit
  • Plug-and-play USB interface to configure relay settings and access data logs on a PC, no drivers or software installation required
  • Service mode to allow relay testing without tripping
  • Eighteen LEDs indicate relay and sensor status
  • DIN-rail and surface mounting
  • Five year warranty

Data Sheets:

Manuals:

Technical Documentation

Typical Applications:
  • Used in new equipment and retrofit applications with all horizontal and vertical bus bars, breaker compartments, drawers, and anywhere that there is potential for an arc-fault.

Minimum System Components:
  • The PGR-8800 Arc-Flash Relay requires input from a light sensor. The built-in sensor can be used, although at least one PGA-LS10 or PGA-LS20 light sensor is typical; 1 or 2 sensors per cubicle of protected equipment are generally recommended.
  • External phase CTs are available to provide overcurrent protection and enhance the reliability of arc-flash detection.
  • The PGR-8800 can be programmed through the software included on the relay, by connecting to a PC with the USB port. No drivers or software installation is required.

IEEE Device Numbers:
50, AFD


Accessories:

PGA-LS10
Point Sensor
Line-of-sight light sensor detects an arc as small as 3 kA within a 2-m half-sphere.
PGA-LS10: Point Sensor
PGA-LS10
Point Sensor
Sensor Indication: Health and Trip indication
Used with: PGR-8800
PGA-LS20
Fiber-Optic Sensor
360-degree light sensor for tricky installations with many shadows or to run along bus bars.
PGA-LS20: Fiber-Optic Sensor
PGA-LS20
Fiber-Optic Sensor
Sensor Indication: Health and Trip indication
Used with: PGR-8800



Current Transformers:
CT200
Current Transformer
Current transformer used to detect phase or ground-fault current.
CT200: Current Transformer
CT200
Current Transformer
Dimensions: 55-mm (2.2") ID window.
Ratio: 200:5 A
Used with: FPS, FPU-32, IDM-3, MPU-32, MPS,
PGR-8800, SE-105, SE-107, SE-325, SE-330,
SE-330HV, SE-701
CT200L
Current Transformer
Current transformer used to detect phase or ground-fault current.
CT200L: Current Transformer
CT200L
Current Transformer
Dimensions: 89-mm (3.5") ID window.
Ratio: 200:5 A
Used with: FPS, FPU-32, IDM-3, MPU-32, MPS,
PGR-8800, SE-105, SE-107, SE-701